Description
FEW325
- Bore Diameter: 100 DN 100 (4 in.)
- Liner Material: H Hard rubber
- Electrode Design: 1 Standard
- Measuring Electrodes Material: D Hastelloy C-4 (2.4610)
- Grounding Accessories : 4 2x Potential Equalizing Rings (Stainless Steel)
- Process Connection Type: A1 Flanges ANSI / ASME B16.5 / 16.47 series B Class 150
- Process Connection Material: B Carbon steel
- Usage Certifications: 1 Standard (without PED)
- Calibration Type: A Standard factory calibration
- Temperature Range of Installation / Ambient: 1 Standard design / -20 ... 60 °C (-4 ... 140 °F)
Temperature Range
- Name Plate: A Adhesive label
- Signal Cable Length and Type: 2 10 m (approx. 30 ft) cable
- Explosion Protection Certification: P usFMc Div. 2
- Protection Class Transmitter / Protection Class: 2 IP 67 (NEMA 4X) / IP 68 (NEMA 6P), cable not fitted and Sensor not potted, sensor is IP67 with PTFE liner
- Cable Conduits: B NPT 1/2 in.
- Power Supply: 3 100 ... 230 V AC, 60 Hz
- Input and Output Signal Type: A HART + 20 mA + Pulse + Contact output
- Configuration Type / Diagnostics Type: 1 Parameters set to factory defaults / Standard diagnostic functions activated
- Documentation Language: M5 English (standard)
- Verification Type: V3 VeriMaster
- Number of Testpoints: T3 3 Points
Downloads